Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis

R. Samsudin, Ahmad Qisti Ramli, A. Berhanuddin, Y. Zaidey

Research output: Chapter in Book/Report/Conference proceedingConference contribution

5 Citations (Scopus)

Abstract

Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The life of the transformer is determined by the condition of the paper insulation. The degradation of the paper insulation will be accelerated with the presence of electrical fault. Electrical fault in power transformer can be categorized into two which are Partial Discharge (PD) and Arcing. A PD will eventually develop into arcing. Any electrical fault in the transformer can be detected by using Dissolved Gas Analysis technique. The DGA can be used to differentiate between the types of faults in the transformer. However, DGA alone is not conclusive in determining the electrical fault in the transformer. As a complement, acoustic partial discharge technique was used to detect the electrical fault in the transformer. In this paper, the detection of electrical fault in two units of 33/11kV, 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. During the acoustic partial discharge testing, some electrical discharge signal was picked-up from On-Load Tap Changer (OLTC) tank. Then, the transformers were un-tanking for physical inspection. Based on the inspection done on two transformers, the DGA analysis methods were unable to detect the OLTC oil contamination in the main tank oil and it is very dependent on the transformer conservator tank design. The acoustic partial discharge technique proves to be a useful tool in detecting electrical discharges in the power transformer.

Original languageEnglish
Title of host publicationICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment
Subtitle of host publicationAdvancement Towards Global Sustainability
Pages299-305
Number of pages7
DOIs
Publication statusPublished - 01 Dec 2009
Event2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability, ICEE 2009 - Malacca, Malaysia
Duration: 07 Dec 200908 Dec 2009

Other

Other2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability, ICEE 2009
CountryMalaysia
CityMalacca
Period07/12/0908/12/09

Fingerprint

Gas fuel analysis
Partial discharges
Power transformers
Acoustics
Insulation
Inspection
Oil tanks
Contamination
Degradation
Testing

All Science Journal Classification (ASJC) codes

  • Renewable Energy, Sustainability and the Environment
  • Environmental Engineering

Cite this

Samsudin, R., Ramli, A. Q., Berhanuddin, A., & Zaidey, Y. (2009). Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis. In ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability (pp. 299-305). [5398629] https://doi.org/10.1109/ICEENVIRON.2009.5398629
Samsudin, R. ; Ramli, Ahmad Qisti ; Berhanuddin, A. ; Zaidey, Y. / Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis. ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability. 2009. pp. 299-305
@inproceedings{824e43991cb34d358fd3eccb71823a01,
title = "Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis",
abstract = "Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The life of the transformer is determined by the condition of the paper insulation. The degradation of the paper insulation will be accelerated with the presence of electrical fault. Electrical fault in power transformer can be categorized into two which are Partial Discharge (PD) and Arcing. A PD will eventually develop into arcing. Any electrical fault in the transformer can be detected by using Dissolved Gas Analysis technique. The DGA can be used to differentiate between the types of faults in the transformer. However, DGA alone is not conclusive in determining the electrical fault in the transformer. As a complement, acoustic partial discharge technique was used to detect the electrical fault in the transformer. In this paper, the detection of electrical fault in two units of 33/11kV, 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. During the acoustic partial discharge testing, some electrical discharge signal was picked-up from On-Load Tap Changer (OLTC) tank. Then, the transformers were un-tanking for physical inspection. Based on the inspection done on two transformers, the DGA analysis methods were unable to detect the OLTC oil contamination in the main tank oil and it is very dependent on the transformer conservator tank design. The acoustic partial discharge technique proves to be a useful tool in detecting electrical discharges in the power transformer.",
author = "R. Samsudin and Ramli, {Ahmad Qisti} and A. Berhanuddin and Y. Zaidey",
year = "2009",
month = "12",
day = "1",
doi = "10.1109/ICEENVIRON.2009.5398629",
language = "English",
isbn = "9781424451456",
pages = "299--305",
booktitle = "ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment",

}

Samsudin, R, Ramli, AQ, Berhanuddin, A & Zaidey, Y 2009, Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis. in ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability., 5398629, pp. 299-305, 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability, ICEE 2009, Malacca, Malaysia, 07/12/09. https://doi.org/10.1109/ICEENVIRON.2009.5398629

Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis. / Samsudin, R.; Ramli, Ahmad Qisti; Berhanuddin, A.; Zaidey, Y.

ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability. 2009. p. 299-305 5398629.

Research output: Chapter in Book/Report/Conference proceedingConference contribution

TY - GEN

T1 - Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis

AU - Samsudin, R.

AU - Ramli, Ahmad Qisti

AU - Berhanuddin, A.

AU - Zaidey, Y.

PY - 2009/12/1

Y1 - 2009/12/1

N2 - Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The life of the transformer is determined by the condition of the paper insulation. The degradation of the paper insulation will be accelerated with the presence of electrical fault. Electrical fault in power transformer can be categorized into two which are Partial Discharge (PD) and Arcing. A PD will eventually develop into arcing. Any electrical fault in the transformer can be detected by using Dissolved Gas Analysis technique. The DGA can be used to differentiate between the types of faults in the transformer. However, DGA alone is not conclusive in determining the electrical fault in the transformer. As a complement, acoustic partial discharge technique was used to detect the electrical fault in the transformer. In this paper, the detection of electrical fault in two units of 33/11kV, 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. During the acoustic partial discharge testing, some electrical discharge signal was picked-up from On-Load Tap Changer (OLTC) tank. Then, the transformers were un-tanking for physical inspection. Based on the inspection done on two transformers, the DGA analysis methods were unable to detect the OLTC oil contamination in the main tank oil and it is very dependent on the transformer conservator tank design. The acoustic partial discharge technique proves to be a useful tool in detecting electrical discharges in the power transformer.

AB - Power transformer consists of components which are under consistent thermal and electrical stresses. The major component which degrades under these stresses is the paper insulation of the power transformer. The life of the transformer is determined by the condition of the paper insulation. The degradation of the paper insulation will be accelerated with the presence of electrical fault. Electrical fault in power transformer can be categorized into two which are Partial Discharge (PD) and Arcing. A PD will eventually develop into arcing. Any electrical fault in the transformer can be detected by using Dissolved Gas Analysis technique. The DGA can be used to differentiate between the types of faults in the transformer. However, DGA alone is not conclusive in determining the electrical fault in the transformer. As a complement, acoustic partial discharge technique was used to detect the electrical fault in the transformer. In this paper, the detection of electrical fault in two units of 33/11kV, 15MVA transformers were done by using Dissolved Gas Analysis (DGA). Then, the acoustic partial discharge test was carried out to detect the activity and locate the source of the electrical fault. During the acoustic partial discharge testing, some electrical discharge signal was picked-up from On-Load Tap Changer (OLTC) tank. Then, the transformers were un-tanking for physical inspection. Based on the inspection done on two transformers, the DGA analysis methods were unable to detect the OLTC oil contamination in the main tank oil and it is very dependent on the transformer conservator tank design. The acoustic partial discharge technique proves to be a useful tool in detecting electrical discharges in the power transformer.

UR - http://www.scopus.com/inward/record.url?scp=77949583026&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=77949583026&partnerID=8YFLogxK

U2 - 10.1109/ICEENVIRON.2009.5398629

DO - 10.1109/ICEENVIRON.2009.5398629

M3 - Conference contribution

SN - 9781424451456

SP - 299

EP - 305

BT - ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment

ER -

Samsudin R, Ramli AQ, Berhanuddin A, Zaidey Y. Field experience of transformer untanking to identify electrical faults and comparison with dissolved gas analysis. In ICEE 2009 - Proceeding 2009 3rd International Conference on Energy and Environment: Advancement Towards Global Sustainability. 2009. p. 299-305. 5398629 https://doi.org/10.1109/ICEENVIRON.2009.5398629